Operating Instructions SWT-2000 DYNALCO
22
6.7.12 Copy Parameter Set
Go to <Configuration>, <Copy from Control A>.
A Parameter set may only be copied from Parameter set A. The following Parameters will be copied:
- Machine factor 1 and 2
- Difference
- Math Function selection
- Upper and Lower Limits in System Limits
- System Limit inversion
- Inclusion of input in the logical combination
- Inclusion of Sensor alarm in the logical combination
- Relay / Open Collector assignment
- Relay / Open Collector latch mode
- Relay / Open Collector fail safe mode
- Analog output assignment
- 0..20mA or 4..20mA setting
- Start and End values
- Analog output time constant
6.7.13 Change-Over Delay
Go to <Configuration>, <Delay>.
One change-over delay may be set for the delay in switching from Parameter set B to Parameter set A only.
Delay time: 0 … 2000 Seconds
Only integer values can be used for the change-over delay.
6.8 Settings
6.8.1 Ethernet Interface
Go to <Settings>, <Interface …>.
No settings can be made. The PC- SWT-2000 connection is Peer to Peer
(PC to PC). SWT-2000’s cannot be connected to a network!
For technical data see Paragraph 2.5.1 Ethernet.
DHCP Server ON / OFF
TCP/IP Adresse 192.168.1.127
TCP/IP Maske 255.255.255.0